Cookie Img
Back to top
   Call Me Free Offline Send SMS Send Inquiry
Home » Products » Three Phase Secondary Current Injection Test Set » Three Phase Secondary Current Injection Test Set

Three Phase Secondary Current Injection Test Set

Three Phase Secondary Current Injection Test Set
Three Phase Secondary Current Injection Test Set
Product Code : MP3000A1H
Brand Name : MYRIAD INDUSTRIAL SOLUTIONS LLP
Price And Quantity
  • Minimum Order Quantity
  • 1
  • Unit of Measure
  • Piece/Pieces
  • Minimum Order Quantity
Trade Information
  • Payment Terms
  • Telegraphic Transfer (T/T), Others
  • Supply Ability
  • as per order Per Month
  • Delivery Time
  • 4 Week
  • Packaging Details
  • Packing in Cardboard boxes
  • Main Export Market(s)
  • Asia, Australia, Central America, North America, South America, Eastern Europe, Western Europe, Middle East, Africa
  • Main Domestic Market
  • All India
Product Description
We are a well known exporter, importer, trader, service provider and distributor of Three Phase Secondary Current Injection Test Set. This testing equipment is useful in testing cover current, earth fault, directional over current, over voltage, under frequency, DFDT, over under voltage, differential and distance protection schemes. The machine's advanced DSP based technology helps it to generate fault signal. The offered machine is equipped with independent voltage generators ans additional voltage generators can also be configured to generate 3U0. The offered test set is packed with integrated LCD front panel and keyboard that can be controlled by PC based software. We also offer optional accessories like inbuilt GPS, generator and additional analog input module with this product. The important technical details of Three Phase Secondary Current Injection Test Set include –

Configurations :

  • MP3000 A1/A1H, MP3000 B1/MP3000 B1H are front panel controlled based on

  • Integrated industrial pc and 8.4 '' LCD customized Windows CE and keypad.

  • MP3000 A /AH /B /BH /C /CH are PC controlled versions

  • MP3000A : 6 x 30A, 4 x 125 V, 0-265 V Aux dc, 0-3 A high burden current output, 8 bin

  • Inputs, 4 bin outputs.

  • MP3000AH : 6 x 30A, 4 x 300 V, 0-265 V Aux dc, 0-3 A high burden current output, 8 bin

  • Inputs, 4 bin outputs.

  • MP3000B : 6 x 30A, 8 x 125 V, 8 bin inputs, 4 bin outputs.

  • MP3000BH : 6 x 30A, 8 x 300 V, 8 bin inputs, 4 bin outputs.

  • MP3000C : 9 x 30A, 4 x 125 V, 8 bin inputs, 4 bin outputs.

  • MP3000CH : 9 x 30A, 4 x 300 V, 8 bin inputs, 4 bin outputs.

  • All the models have front panel visual and audio indication about the output status. Current generators are short circuit protected, voltage generators are overload protected.

Product Specifications :

  • Current generators : Six Independent generators in two groups.

  • Each group is of 3 generators with common neutral.

  • Max current : 30 A AC- 20 A dc

  • Resolution : 0.03m A (0-0.3 A). 0.3m A (0.3-3.0 A). 1.0m A (3.0 -30A)

  • Accuracy : Error ≤ 0.1% of setting value. (I ≥ 0.2 A) error < 0.1% of setting value ± 200 µa. (I < 0.2 A)

  • Harmonic distortion : 0.2 A -30 A≤ 0.2%

  • Response time : ≤100µS

  • Power : 5A : 60 VA. 30 A : 350 VA max

  • Output Time : Continuous (I ≤ 10 A). 100S (10 A < I≤20 A) > 20 S (20A Voltage generators :Four Independent generators with common neutral.4th voltage generator can be 3U0 or independent.

  • Max voltage AC : 125V L-N/ 250 V L-L (MP3000F). 300V L-N/600V L-L (MP3000FH)

  • Amplitude range of DC : ± 176 V (MP3000F), ± 424 V (MP3000FH)

  • Resolution : 4 mV (MP3000F), 10 mV (MP3000FH)

  • Accuracy : Error ≤0.1% of setting from 10 V …125V (MP3000F).Error ≤0.1% of setting from 24 V …300V (MP3000FH)

  • Harmonic distortion : ≤ 0.2%(10- 125 V..MP3000F) ≤ 0.2% (24- 300 V MP3000FH)

  • Response time : ≤100µS

  • Power : ≥ 40 VA (57V). ≥100VA (100V- 300V)

  • Output time : Continuous

  • Frequency :

    • Range (sine wave) : DC...1000 Hz

    • Range (transient ) : DC…3000 Hz

  • Accuracy : 0.01%

  • Resolution : 0.001 Hz

  • Phase angle :

    • Range : -3600…+3600

    • Accuracy : ≤0.20

    • Resolution : 0.050

  • Aux DC :

    • Range : 0-265 V Variable, Independently controlled

    • Power : 100 W max

  • High Burden Current Output :

    • Range : 0-3 AMP

    • Power : 100 VA

  • Max Voltage : 100 V

  • Max Binary Input : Can trigger by GPS

  • Numbers : 8

  • Input sensing : Automatically detects the changeover of a dry or a wet contact

  • Sensing range : Wet contact( 24- 250V DC)

  • Resolution : 50 µS

  • Max. measuring time : Up to 99,999 S

  • Binary output :

    • Numbers :4

    • Type : Potential free

General specifications :

  • National standard : DL/T624-1997

  • AC Mains input voltage range : 110- 265 V

  • AC Mains voltage frequency : 45- 65 Hz

  • Operating temperature : -5 TO +50o C

  • Relative Humidity : 5-95% non condensing

  • Interface : Ethernet for PC connection, Optical for 61850

  • EMC : EN 61326-1 : 2006

  • EN 61000-3-2 : 2006

  • EN 61000-3-3 : 1995 + A1 : 2001+ A2 :2005 FCC Part 15 Class A

  • LVD : EN 61010-1 :2001

  • Max Power Consumption : 2000VA at 230 V; 1000VA at 115 V

  • Standard accessories :Test lead set and connectors with a canvas carry bag. Shoulder carry bag for MP3000. Transportation case.

  • Optional features : Contact us before order

  • Analog inputs :One dc current : 0-20 mA , Resolution 2 µA , Accuracy : 0.05%

  • One DC voltage : ± 10 V, Resolution :1 mV, Accuracy : 0.05%

  • Integrated GPS : For end to end test




MYRIAD INDUSTRIAL SOLUTIONS LLP

Contact Us

( *represents compulsory fields )

Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.



MYRIAD INDUSTRIAL SOLUTIONS LLP
Mumbai, Maharashtra, India
A-401, Vini Gardens-II, Off Mandapeshwar Road, Near Mary Immaculate School, Dahisar West, Mumbai - 400068, Maharashtra, India
Mr. Sunildatt V. Limaye (CEO)
Trust Stamp
Product Showcase
   Call Me Free Offline Send SMS Send Inquiry